Simulation Analysis of Intermittent Arcing Ground Faults in Urban Distribution Networks
编号:13 访问权限:仅限参会人 更新:2023-11-20 13:45:32 浏览:497次 口头报告

报告开始:2023年12月09日 09:30(Asia/Shanghai)

报告时间:15min

所在会场:[S4] Power system and automation [S4] Power system and automation

演示文件

提示:该报告下的文件权限为仅限参会人,您尚未登录,暂时无法查看。

摘要
This article establishes a transient simulation model for urban distribution networks with intermittent arc grounding faults for arc suppression coil grounding systems. The simulation analyzes the impact of arc suppression coils on arc grounding overvoltage from three aspects: compensation degree, response speed, and exit speed. The simulation results show that the suppression effect of intermittent arc overvoltage is the best when the arc suppression coil operates in a state close to full compensation; After an intermittent grounding fault occurs, immediately switch on the arc suppression coil, which can effectively suppress the overvoltage caused by the next arc after the arc is extinguished; If the arc suppression coil is not exited in a timely manner, it may cause the problem of series resonance overvoltage. Finally, a suppression strategy for arc grounding overvoltage in the arc suppression coil grounding system is proposed.
关键词
Distribution Network,Intermittent Arc Grounding,Transient Simulation