High voltage power cable defect diagnosis based on the whole cable dielectric spectrum test
Xiaokai Meng1, Zhumao Lu1, Hua Yu1, Wei Wang*2, Haoyue Wang2, Maolun Sun2
1. State Grid Shanxi Electric Power Company Electric Power Research Institute, 2. North China electric power university
ww790324@163.com
Purpose
Dielectric spectrum testing is an effective means of finding cable defects. But traditional dielectric spectrum testing requires cable slice sampling, which is very expensive for high voltage power cables. Therefore, this paper explores the method of whole cable testing of high voltage power cables.
Experimental
Due to the large capacitance of the whole cable test, and the current research shows that the low frequency band has a higher sensitivity to reflect cable defects, the test frequency band of the dielectric spectrum is set to 0.01Hz-0.1Hz. Three 110kV power cables with defects were prepared, and the dielectric spectrum measurements of the whole cables were carried out. Restricted by the output voltage of the device, the maximum test voltage is 1/3U
0.
Results
The dielectric loss from 0.1Hz-0.05Hz-0.02Hz-0.01Hz under four output voltages of 1/10 U
0-1/5 U
0-1/4U
0-1/3 U
0 was obtained.
Conclusions
The research results show that it is feasible to diagnose high-voltage cables by measuring the dielectric spectrum of the whole cable. Although the highest voltage is only 1/3U
0, the dielectric spectra of different defect types have significant differences, which can be diagnosed and identified.