708 / 2022-03-31 16:45:30
Study of the Long-Time Arcing Characteristics of SF6 in a ±800KV High Speed Switch
MHD,arc burning,SF6,high-speed disconnecting switch,arc extinguishing chamber
终稿
Jinzhuang Lv / Maintenance & Test Center of EHV Power Transmission Company of China Southern Power Grid
Junwei Deng / Xi’an Jiaotong University;State Key Laboratory of Electrical Insulation and Power Equipment
Changhong Zhang / Maintenance & Test Center of EHV Power Transmission Company of China Southern Power Grid
Xingwen Li / Xi'an Jiaotong University;State Key Laboratory of Electrical Insulation and Power Equipment
Boya Zhang / Xi’an Jiaotong University;State Key Laboratory of Electrical Insulation and Power Equipment
Gulin Xia / Maintenance & Test Center of EHV Power Transmission Company of China Southern Power Grid
Maoheng Jing / Maintenance & Test Center of EHV Power Transmission Company of China Southern Power Grid
Boyi Fang / Liuzhou Bureau of EHV Power Transmission Company of China Southern Power Grid
Weiguo Li / Maintenance & Test Center of EHV Power Transmission Company of China Southern Power Grid
Xu Yang / Maintenance & Test Center of EHV Power Transmission Company China Southern Power Grid
With the growing capacity of DC transmission systems, disconnecting switch with the abilities of interruption have been requested more strictly. High-speed disconnecting switch (HSS) is a new type of switch equipment that has received widespread attention in the world. However, the research on the arc extinguishing chamber of HSS during arcing is still in its infancy in our country. Therefore, the paper carries out the arcing simulation to study the long-time (400ms) arcing characteristics, around the core problem of optimization of extinguishing chamber structure.

In this paper, firstly, based on the magneto-hydro-dynamic (MHD) modeling method, the 2-D model of arc burning process is established for the structure of ±800KV HSS, considering the high-speed dynamic motion process of the contact. Secondly, According to real gas model,the actual gas attributes of SF6 are loaded into the governing equations for calculation. Then, focusing on the dynamic temporal and spatial distribution of long-time arc burning, we can analyze the influence of arc energy on pressure, temperature and voltage under different conditions.

The results about the distribution law of arc energy and temperature, pressure and velocity are calculated for the evaluation of the performance of arc burning. The simulation results are in agree with the experimental results. Some optimization methods for arc extinguishing chamber of HSS are proposed by simulation.

The established model in this thesis is valid and simulation results are expected to enrich the understanding of the long-time arcing characteristics. The work of this paper is significant and can provide a theoretical basis and technical guidance for engineering application in disconnecting Switch.