218 / 2021-11-02 13:53:50
Partial Discharge Ultrasonic Signal Detection in Transformer Bushing Based on Mach-Zehnder Fiber Optic Interferometer
Partial discharge; ultrasonic; optical-fiber sensor; Mach-Zehnder interference; transformer bushing
终稿
Rongbin Shi / North China Electric Power University
Sihan Wang / North China Electric Power University
Zhongqin Lin / North China Electric Power University
炜淇 秦 / 华北电力大学
Shuguo Gao / State Grid Hebei Electric Power Research Institute
Chao Xing / State Grid Hebei Electric Power Research Institute
国明 马 / 华北电力大学新能源电力系统国家重点实验室
Oil-impregnated paper (OIP) bushings are widely used in the power system. In order to detect the weak signal generated by the partial discharge (PD) in bushing online, a fiber-optic ultrasonic sensing system based on Mach-Zehnder interference (MZI) was studied in this paper. The average sensitivity of the OFS is 67.3 dB (0 dB=1 V(m·s-1)). The performance test of the fiber-optic ultrasonic sensor (OFS) was carried out on a real 110 kV transformer bushing. PD signal was detected by the proposed MZI fiber-optic ultrasonic sensor, when the average discharge volume is 10.4 pC. The experimental results show that the interferometric fiber-optic ultrasonic sensing system can be used for transformer bushing PD ultrasonic signal detection.  It is of great significance to improve the maintenance of the transformer bushing
重要日期
  • 会议日期

    07月11日

    2023

    08月18日

    2023

  • 11月10日 2021

    初稿截稿日期

  • 12月10日 2021

    注册截止日期

  • 12月11日 2021

    报告提交截止日期

主办单位
IEEE IAS
承办单位
IEEE IAS Student Chapter of Southwest Jiaotong University (SWJTU)
IEEE IAS Student Chapter of Huazhong University of Science and Technology (HUST)
IEEE PELS (Power Electronics Society) Student Chapter of HUST
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询