Short Circuit Impedance Analysis for Cross-Coupling AT Power Traction Network Under Over-zone Feeding Operation Condition
Impedance analysis; Over-zone feeding operation condition; Cross-coupling AT power supply; Equivalent circuit.
终稿
Zhang Shuo / Southwest jiaotong university postgraduate
Lin Guosong / Southwest Jiaotong University
Li Yuan / Southwest jiaotong university postgraduate
 The cross-coupling AT (Autotransformer) power supply mode is applied on high-speed railways in China. When the power failure of traction substation is caused by the incoming power supply or equipment failure, the traction network needs to adopt the over-zone feeding operation condition to ensure the continuous power supply It is necessary to analyze the short circuit impedance of traction network under over-zone feeding operation condition. It provides a useful reference for the analysis of relay protection and power supply capacity of the traction network. In this paper, the equivalent circuit method is used to build the circuit model of cross-coupling AT power traction network under over-zone feeding operation condition, and the relationship between short circuit impedance and distance is deduced. The relation characteristics of short circuit impedance and distance is explained. The simulation result based on Matlab/Simulink shows that the application of equivalent circuits and the derivation of short circuit impedance formula are verified.
重要日期
  • 会议日期

    07月11日

    2023

    08月18日

    2023

  • 11月10日 2021

    初稿截稿日期

  • 12月10日 2021

    注册截止日期

  • 12月11日 2021

    报告提交截止日期

主办单位
IEEE IAS
承办单位
IEEE IAS Student Chapter of Southwest Jiaotong University (SWJTU)
IEEE IAS Student Chapter of Huazhong University of Science and Technology (HUST)
IEEE PELS (Power Electronics Society) Student Chapter of HUST
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询