118 / 2021-08-18 17:36:17
Damage Analysis of Oil-Filled Submarine Cable in Suspended State under Wave-Current Force Based on Finite Element Simulation
终稿
Jingwen Zhang / Xi'an Jiaotong University
Yu Chen / Xi'an Jiaotong University
Feng JIA / Xi'an Jiaotong University
Yifang Zhou / Xi'an Jiaotong University
Hanzhi Li / Xi'an Jiaotong University
Changxi Li / Xi'an Jiaotong University
Xiaowei Huang / Ltd.;Guangzhou Bureau,EHV Transmission Company of China Southern Power Grid Co.
Qiang Guo / Ltd.;Guangzhou Bureau; EHV Transmission Company of China Southern Power Grid Co.
In this paper, 500kV AC submarine cable was taken as the object, the finite element software COMSOL was used to establish the simulation model of fluid-structure coupling, and the force of the suspended submarine cable was analyzed. The stress distribution of the lead alloy sheath of the cable in four specific directions and the location of the maximum stress value was obtained. On this basis, the relationship between the suspended length and the stress value was obtained by changing the suspended length of the submarine cable. According to the initial yield stress value of the lead alloy sheath, the reference suspended length of the preliminary damaged cable structure was given, which provides some theoretical analysis for the online monitoring of the submarine cable.  The results show that when the suspended length reaches 7.05 meters, the maximum stress value of the lead alloy sheath at the initial yield stress is 1.97×107(N/m2). 

 
重要日期
  • 会议日期

    10月21日

    2021

    10月23日

    2021

  • 10月26日 2021

    注册截止日期

主办单位
Southeast University, China
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询