Partial Discharge Detection on 80 kV DC XLPE Cable with Artificial Defects under DC Voltage
partial discharge, HVDC systems, diagnosis, XLPE, partial discharge inception voltage (PVID), x-ray
摘要待审
Haitian Wang / Global Energy Interconnection Research Institute Europe GmbH
Mingyu Zhou / Global Energy Interconnection Research Institute Europe GmbH
Extruded cross-linked polyethylene (XLPE) cables have become the preferred choice for the VSC-HVDC, due to benefits like easier production, transportation, and installation compared with MI cable. For AC cables, partial discharge testing is a vital method to evaluate the condition of the cable. However, there is significantly less experience regarding the behavior of partial discharge under DC conditions. It is well known that failures arise more often in accessories than in the cable itself. In order to evaluate partial discharges for a typical installation defect, a sharp transition edge between the outer semicon and the insulation layer has been prepared on an 80kV DC-cable system. Under different cable conductor temperatures, partial discharge tests with DC voltage steps have been performed with and without pulsed X-ray. For comparison, PD measurements at AC have also been performed on the DC-cable. Finally, the partial discharge inception voltage (PDIV) under DC and AC has been compared, and the dependence of temperature and X-ray pulses for DC partial discharge is investigated.
重要日期
  • 会议日期

    09月06日

    2020

    09月10日

    2020

  • 03月31日 2020

    摘要截稿日期

  • 06月30日 2020

    初稿截稿日期

  • 07月15日 2020

    初稿录用通知日期

  • 08月10日 2020

    终稿截稿日期

  • 08月10日 2020

    提前注册日期

  • 08月23日 2020

    注册截止日期

主办单位
IEEE
清华大学
IEEE电介质和电气绝缘协会
承办单位
清华大学
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询