866 / 2019-04-30 10:07:47
Influence of Power Factor on Small-Signal Stability of Grid-Connected Converter Systems
power factor,small-signal stability,admittance model,voltage-source converter (VSC),single-input single-output (SISO)
全文录用
Luyao Xu / College of electrical engineering, Zhejiang University
Minghui Sun / College of electrical engineering, Zhejiang University
Xiaozhe Song / State Grid Jilin Electric Power Company Limited
Chunhua Wang / State Grid Jilin Electric Power Company Limited
Huanhai Xin / College of electrical engineering, Zhejiang University
This paper proposes a novel admittance model for a grid-connected voltage-source converter (VSC) system in polar frame. In the admittance model, the power factor of VSC can be explicitly expressed and the influence of power factor on stability can be analyzed intuitively. Based on this admittance model, the grid-connected VSC system can be modelled as a single-input single-output (SISO) system. Moreover, from a small-signal stability perspective, we prove that when controllers’ parameters are fixed, a change of the VSC’s power factor can be equivalent to a change of the grid’s impedance. The validity of the model and analysis is verified by simulation results.